MODEL NO. | CATALOG NO. | PHASE | TYPE | FRAME |
CK14 | C125P2CS | 3 | TCE | 444TS |
ORDER NO. | 19223 | LINE NO. |
MPI: | 270734 |
HP: | 125 |
POLES: | 4 |
VOLTS: | 460 |
HZ: | 60 |
SERVICE FACTOR: | 1.15 |
EFFICIENCY (%): | |
S.F. | 94.8 |
FULL | 95 |
3/4 | 95.3 |
1/2 | 94.7 |
1/4 | 91.6 |
POWER FACTOR (%): | |
S.F. | 84.6 |
FULL | 83.9 |
3/4 | 81.1 |
1/2 | 73.6 |
1/4 | 53.5 |
NO LOAD | 4.8 |
LOCKED ROTOR | 22.2 |
AMPS: | |
S.F. | 168 |
FULL | 147 |
3/4 | 114 |
1/2 | 84 |
1/4 | 60 |
NO LOAD | 47.6 |
LOCKED ROTOR | 932.8 |
NEMA CODE LETTER | G |
NEMA DESIGN LETTER | B |
FULL LOAD RPM | 1785 |
NEMA NOMINAL / EFFICIENCY (%) | 95 |
GUARANTEED EFFICIENCY (%) | 94.1 |
MAX KVAR | 32.2 |
AMBIENT (°C) | 40 |
ALTITUDE (FASL) | 3300 |
SAFE STALL TIME-HOT (SEC) | 22 |
SOUND PRESSURE (DBA @ 1M) | 72 |
TORQUES: | |
BREAKDOWN{% F.L.} | 264 |
LOCKED ROTOR{% F.L.} | 121 |
FULL LOAD{LB-FT} | 368.1 |
NEMA Nominal and Guaranteed Efficiencies are up to 3,300 feet above sea level and 25 ° C ambient
The Above Data Is Typical, Sinewave Power Unless Noted Otherwise | ||
| NIDEC MOTOR CORPORATION | |
Nidec trademarks followed by the ® symbol are registered with the U.S. Patent and Trademark Office. |