| DATE: | 4/17/2026 | P.O. NO.: | DL29 |
| | | Order/Line NO.: | 21423 MN 100 |
| TO: | | |
| |
| Model Number: | DL29 | | Catalog Number: | H20P3G | | Hostile Duty Pre. Eff. Config. | | CONF,MOTOR,HOSTILE DUTY PRE EF |
| REVISIONS: (NONE) |
| |
| ALL DOCUMENTS HEREIN ARE CONSIDERED CERTIFIED BY NIDEC MOTOR CORPORATION. |
| THANK YOU FOR YOUR ORDER AND THE OPPORTUNITY TO SERVE YOU. |
| Features: |
| Horsepower .............. 00020.00 ~ KW: 14.92 |
| Enclosure ............... TEFC |
| Poles ................... 06 ~ RPM: 1200 |
| Frame Size .............. 286~T |
| Phase/Frequency/Voltage.. 3~060~575 ~ Random Wound |
| Service Factor .......... 1.15 |
| Insulation Class ........ Class "F" ~ Insulife 1000 |
| Altitude In Feet (Max) .. 3300 Ft.(1000 M) |
| Ambient In Degree C (Max) +40 C |
| Assembly Position ....... "F-1" Assembly Position |
| Efficiency Class ........ Premium Efficiency |
| Application ............. Unknown |
| Customer Part Number .... |
| "AK" Dimension (Inches).. NA |
| Temperature Rise (Sine Wave): "B" Rise @ 1.0 SF (Resist) |
| Starting Method ......... Wye Start-Delta Run |
| Duty Cycle .............. Continuous Duty |
| Efficiency Value ........ 90.2 % ~ Typical |
| Load Inertia (lb-ft2): NEMA ~ NEMA Inertia: 262.00 ~ 1.00 |
| Number Of Starts Per Hour: NEMA |
| Motor Type Code ......... CTE |
| Rotor Inertia (LB-FT²) | 6.23 LB-FT² |
|
| Qty. of Bearings PE (Shaft) | 1 |
|
| Qty. of Bearings SE (OPP) | 1 |
|
| Bearing Number PE (Shaft) | 6310-2Z-J/C3 |
|
| Bearing Number SE (OPP) | 6310-2Z-J/C3 |
|