DATE: | 9/8/2024 | P.O. NO.: | FL19 |
| | Order/Line NO.: | 24076 MN 100 |
TO: | | |
|
Model Number: | FL19 | Catalog Number: | C400P2W | Titan Horizontal TEFC Config. | CONF,MOTOR,TITAN HORIZ TEFC |
| REVISIONS: (NONE) |
|
ALL DOCUMENTS HEREIN ARE CONSIDERED CERTIFIED BY NIDEC MOTOR CORPORATION. |
THANK YOU FOR YOUR ORDER AND THE OPPORTUNITY TO SERVE YOU. |
Features: |
Horsepower .............. 00400.00~00000.00 ~ KW: 298.4 |
Enclosure ............... TEFC |
Poles ................... 04~00 ~ RPM: 1800~0 |
Frame Size .............. 5010~S |
Phase/Frequency/Voltage.. 3~060~2300/4000 |
Winding Type ............ Form Wound |
Service Factor .......... 1.15 |
Insulation Class ........ Class "F" ~ Insulife 5000 |
Altitude In Feet (Max) .. 3300 Ft.(1000 M) |
Ambient In Degree C (Max) +40 C |
Assembly Position ....... "F-1" Assembly Position |
Efficiency Class ........ Premium Efficiency |
Application ............. Centrifugal Pump |
Customer Part Number .... |
Self Certified Div 2 Info: |
Division 2 ~ Class I ~ Group A, B, C & D |
Class II N/A ~ Group N/A ~ T3 Temp Code |
Zone 2 Required? Y/N No |
Div 2 Service Factor ... 1.00 |
"AK" Dimension (Inches).. NA |
Temperature Rise (Sine Wave): "B" Rise @ 1.0 SF (Resist) |
Design Letter ........... B |
KVA Code Letter ......... "G" |
Starting Method ......... Direct-On-Line Start |
Duty Cycle .............. Continuous Duty |
Efficiency Value ........ 95.0 % ~ NEMA Nominal |
Sound Pressure Required (dBA) 85 dBa @ 1M Sound Pressure |
Load Inertia: NEMA ~ Standard Inertia: 1546 LB-FT2 |
Number Of Starts Per Hour: NEMA |
Motor Type Code ......... JCE |
Rotor Inertia (LB-FT²) | 192. LB-FT² |
|
Qty. of Bearings PE (Shaft) | 1 |
|
Qty. of Bearings SE (OPP) | 1 |
|
Bearing Number PE (Shaft) | 6315-J/C3 |
|
Bearing Number SE (OPP) | 6315-J/C3 |
|