| DATE: | 11/14/2025 | P.O. NO.: | GB69 |
| | | Order/Line NO.: | 27259 MN 100 |
| TO: | | |
| |
| Model Number: | GB69 | | Catalog Number: | MHD18P1Y3001L | | Hostile Duty Config IEC | | CONF,MOTOR,HOSTILE DUTY,IEC |
| REVISIONS: (NONE) |
| |
| ALL DOCUMENTS HEREIN ARE CONSIDERED CERTIFIED BY NIDEC MOTOR CORPORATION. |
| THANK YOU FOR YOUR ORDER AND THE OPPORTUNITY TO SERVE YOU. |
| Features: |
| Horsepower .............. 00024.80~00000.00 |
| Kilowatts ............... 00018.50~00000.00 |
| Enclosure ............... IC411 TE Fan Cooled - IP55 |
| Poles ................... 02~00 ~ RPM: 3000~0 |
| Frame Size .............. 160~B5 |
| Phase/Frequency/Voltage.. 3~050~230/400 |
| Winding Type ............ Random Wound |
| Service Factor .......... 1.00 |
| Thermal (Insulation) Class 155 C / Class "F" ~ Insulife 1000 |
| Altitude In Meters (Max). 1000 M |
| Ambient In Degree C (Max) +40 C |
| Mounting Arrangement ... B5L (IM3001) |
| Efficiency Class ........ IE3 Efficiency |
| Application ............. Unknown |
| Customer Part Number .... |
| Self Certified Div 2 Info: |
| Division 2 ~ Class I ~ Group A, B, C & D |
| Class II ~ Group F ~ T3 Temp Code |
| Zone 2 Required? Y/N Yes |
| Div 2 Service Factor ... 1.00 |
| IIA IIB IIC |
| IEC "N" Dimension ....... 250 |
| Temperature Rise (Sine Wave): "B" Rise @ 1.0 SF (Resist) |
| Starting Method ......... Direct-On-Line Start |
| Duty Cycle .............. Continuous Duty |
| Efficiency Value ........ 92.4 % ~ Typical IEC |
| Load Inertia: IEC ~ Standard Inertia: .552 KG-M2 |
| Number Of Starts Per Hour: IEC |
| Motor Type Code ......... ICTEF |
| Rotor Inertia (Kg-M²) | 9.12 Kg-M² |
|
| Qty. of Bearings PE (Shaft) | 1 |
|
| Qty. of Bearings SE (OPP) | 1 |
|
| Bearing Number PE (Shaft) | 6309-2Z-J/C3 |
|
| Bearing Number SE (OPP) | 6209-2Z-J/C3 |
|