| DATE: | 1/16/2026 | P.O. NO.: | GM59 |
| | | Order/Line NO.: | 26310 MN 100 |
| TO: | | |
| |
| Model Number: | GM59 | | Catalog Number: | CW30V2E2 | | Corro-Duty VFD Duty Config. | | CONF,MOTOR,CORRO-DUTY VFD DUTY |
| REVISIONS: (NONE) |
| |
| ALL DOCUMENTS HEREIN ARE CONSIDERED CERTIFIED BY NIDEC MOTOR CORPORATION. |
| THANK YOU FOR YOUR ORDER AND THE OPPORTUNITY TO SERVE YOU. |
| Features: |
| Horsepower .............. 00030.00 ~ KW: 22.38 |
| Enclosure ............... TEFC |
| Poles ................... 04 ~ RPM: 1800 |
| Frame Size .............. 286~T |
| Phase/Frequency/Voltage.. 3~060~230/460 |
| Winding Type ............ Random Wound |
| Service Factor .......... 1.15 |
| Insulation Class ........ Class "F" ~ Insulife 2000 |
| Altitude In Feet (Max) .. 3300 Ft.(1000 M) |
| Ambient In Degree C (Max) +40 C |
| Assembly Position ....... "F-2" Assembly Position |
| Efficiency Class ........ Premium Efficiency |
| Application ............. Cooling Tower Duty |
| Inverter Duty NEMA MG1 Part 31 |
| Customer Part Number .... |
| Secondary Rating: |
| 30 Horsepower ~ 50 Hertz ~ 200/400 Volts |
| Inverter Duty Rating Details: |
| Load Type (Base Hz & Below) .. Variable Torque |
| Speed Range (Base Hz & Below). 20:1 |
| VFD Service Factor 1.00 |
| "AK" Dimension (Inches).. NA |
| Temperature Rise (Sine Wave): "B" Rise @ 1.0 SF (Resist) |
| Starting Method ......... Direct-On-Line Start |
| Duty Cycle .............. Continuous Duty |
| Efficiency Value ........ 93.6 % ~ Typical |
| Load Inertia: NEMA ~ Standard Inertia: 144 LB-FT2 |
| Number Of Starts Per Hour: NEMA |
| Motor Type Code ......... TCI |
| Rotor Inertia (LB-FT²) | 3.69 LB-FT² |
|
| Qty. of Bearings PE (Shaft) | 1 |
|
| Qty. of Bearings SE (OPP) | 1 |
|
| Bearing Number PE (Shaft) | 6310-2RS-J/C3 |
|
| Bearing Number SE (OPP) | 6210-2RS-J/C3 |
|