DATE: | 12/7/2024 | P.O. NO.: | HK36 |
| | Order/Line NO.: | 27217 MN 100 |
TO: | | |
|
Model Number: | HK36 | Catalog Number: | U5V2CC3ID12 | Unimount Inverter Duty Config. | CONF,MOTOR,UNIMOUNT VFD DUTY |
| REVISIONS: (NONE) |
|
ALL DOCUMENTS HEREIN ARE CONSIDERED CERTIFIED BY NIDEC MOTOR CORPORATION. |
THANK YOU FOR YOUR ORDER AND THE OPPORTUNITY TO SERVE YOU. |
Features: |
Horsepower .............. 00005.00 ~ KW: 3.73 |
Enclosure ............... TEFC |
Poles ................... 04 ~ RPM: 1800 |
Frame Size .............. 184~TC |
Phase/Frequency/Voltage.. 3~060~460 |
Winding Type ............ Random Wound |
Service Factor .......... 1.15 |
Insulation Class ........ Class "F" ~ Insulife 2000 |
Altitude In Feet (Max) .. 3300 Ft.(1000 M) |
Ambient In Degree C (Max) +40 C |
Assembly Position ....... "F-3" Assembly Position |
Efficiency Class ........ Premium Efficiency |
Application ............. Unknown |
Integrated Inverter Drive~ |
Customer Part Number .... |
Inverter Duty Rating Details: |
Load Type (Base Hz & Below) .. Variable Torque |
Speed Range (Base Hz & Below). 6:1 |
VFD Service Factor 1.15 |
"AK" Dimension (Inches).. 8.500 |
Temperature Rise (Sine Wave): "F" Rise @ SF (Resist) |
Starting Method ......... VFD Start Only |
Duty Cycle .............. Continuous Duty |
Efficiency Value ........ 89.5 % ~ Typical |
Load Inertia: NEMA ~ Standard Inertia: 27 LB-FT2 |
Number Of Starts Per Hour: NEMA |
Motor Type Code ......... UTI |
Rotor Inertia (LB-FT²) | .405 LB-FT² |
|
Qty. of Bearings PE (Shaft) | 1 |
|
Qty. of Bearings SE (OPP) | 1 |
|
Bearing Number PE (Shaft) | 6206-2Z-J/C3 |
|
Bearing Number SE (OPP) | 6205-2Z-J/C3 |
|