| MODEL NO. | CATALOG NO. | PHASE | TYPE | FRAME |
| DU67 | DJ40E1GP | 3 | FD1 | 286JP |
| ORDER NO. | 22765 | LINE NO. |
| MPI: | 157204 |
| HP: | 40 |
| POLES: | 2 |
| VOLTS: | 575 |
| HZ: | 60 |
| SERVICE FACTOR: | 1.15 |
| EFFICIENCY (%): | |
| S.F. | 92.3 |
| FULL | 91.7 |
| 3/4 | 93.8 |
| 1/2 | 93.5 |
| 1/4 | 90.4 |
| POWER FACTOR (%): | |
| S.F. | 88.4 |
| FULL | 89.3 |
| 3/4 | 89.7 |
| 1/2 | 87.7 |
| 1/4 | 76.8 |
| NO LOAD | 10.4 |
| LOCKED ROTOR | 41.1 |
| AMPS: | |
| S.F. | 42 |
| FULL | 36 |
| 3/4 | 26.7 |
| 1/2 | 18.3 |
| 1/4 | 10.8 |
| NO LOAD | 6.2 |
| LOCKED ROTOR | 228 |
| NEMA CODE LETTER | G |
| NEMA DESIGN LETTER | B |
| FULL LOAD RPM | 3560 |
| NEMA NOMINAL / EFFICIENCY (%) | 93 |
| GUARANTEED EFFICIENCY (%) | 91.7 |
| MAX KVAR | 5.2 |
| AMBIENT (°C) | 40 |
| ALTITUDE (FASL) | 3300 |
| SAFE STALL TIME-HOT (SEC) | 9 |
| SOUND PRESSURE (DBA @ 1M) | 72 |
| TORQUES: | |
| BREAKDOWN{% F.L.} | 225 |
| LOCKED ROTOR{% F.L.} | 198 |
| FULL LOAD{LB-FT} | 59 |
NEMA Nominal and Guaranteed Efficiencies are up to 3,300 feet above sea level and 25 ° C ambient
| The Above Data Is Typical, Sinewave Power Unless Noted Otherwise | ||
| NIDEC MOTOR CORPORATION |
|