MODEL NO. | CATALOG NO. | PHASE | TYPE | FRAME |
DY53 | WDS32P1AC | 3 | SSE | 145TC |
ORDER NO. | NA | LINE NO. |
MPI: | 169021 | 169022 | 169023 |
HP: | 1.5 | 1.5 | 1.5 |
POLES: | 2 | 2 | 2 |
VOLTS: | 460 | 230 | 208 |
HZ: | 60 | 60 | 60 |
SERVICE FACTOR: | 1.15 | 1.15 | 1.15 |
EFFICIENCY (%): | |||
S.F. | 84.4 | 84.4 | 82.5 |
FULL | 84 | 84 | 82.5 |
3/4 | 83.9 | 83.9 | 83.7 |
1/2 | 80.8 | 80.8 | 81.4 |
1/4 | 70.9 | 70.9 | 72.4 |
POWER FACTOR (%): | |||
S.F. | 88.9 | 88.9 | 90.5 |
FULL | 87.3 | 87.3 | 89.6 |
3/4 | 82.7 | 82.7 | 86.4 |
1/2 | 73.4 | 73.4 | 79.2 |
1/4 | 54.2 | 54.2 | 61.4 |
NO LOAD | 16.5 | 16.5 | 18.7 |
LOCKED ROTOR | 66.4 | 66.4 | 65.3 |
AMPS: | |||
S.F. | 2.2 | 4.3 | 4.8 |
FULL | 1.9 | 3.8 | 4.2 |
3/4 | 1.5 | 3 | 3.2 |
1/2 | 1.2 | 2.4 | 2.4 |
1/4 | 0.9 | 1.8 | 1.7 |
NO LOAD | 0.8 | 1.6 | 1.4 |
LOCKED ROTOR | 18.8 | 38 | 33 |
NEMA CODE LETTER | M | M | K |
NEMA DESIGN LETTER | B | B | B |
FULL LOAD RPM | 3510 | 3510 | 3480 |
NEMA NOMINAL / EFFICIENCY (%) | 84 | 84 | 82.5 |
GUARANTEED EFFICIENCY (%) | 81.5 | 81.5 | 80 |
MAX KVAR | 0.5 | 0.5 | 0.4 |
AMBIENT (°C) | 40 | 40 | 40 |
ALTITUDE (FASL) | 3300 | 3300 | 3300 |
SAFE STALL TIME-HOT (SEC) | 12 | 12 | 15 |
SOUND PRESSURE (DBA @ 1M) | 0 | 0 | 0 |
TORQUES: | |||
BREAKDOWN{% F.L.} | 433 | 433 | 348 |
LOCKED ROTOR{% F.L.} | 324 | 324 | 256 |
FULL LOAD{LB-FT} | 2.2 | 2.2 | 2.3 |
NEMA Nominal and Guaranteed Efficiencies are up to 3,300 feet above sea level and 25 ° C ambient
The Above Data Is Typical, Sinewave Power Unless Noted Otherwise | ||
| NIDEC MOTOR CORPORATION | |
Nidec trademarks followed by the ® symbol are registered with the U.S. Patent and Trademark Office. |