| MODEL NO. | CATALOG NO. | PHASE | TYPE | FRAME |
| GK29 | CD200P3F | 3 | TCE | 449T |
| ORDER NO. | 27291 | LINE NO. |
| MPI: | 281901 | 281902 |
| HP: | 200 | 150 |
| POLES: | 6 | 6 |
| VOLTS: | 460 | 400 |
| HZ: | 60 | 50 |
| SERVICE FACTOR: | 1.15 | 1 |
| EFFICIENCY (%): | ||
| S.F. | 95.6 | |
| FULL | 95.8 | 95.9 |
| 3/4 | 96.2 | 96 |
| 1/2 | 95.9 | 95.4 |
| 1/4 | 93.5 | 92.5 |
| POWER FACTOR (%): | ||
| S.F. | 82.3 | |
| FULL | 81.8 | 79.1 |
| 3/4 | 79.1 | 74.2 |
| 1/2 | 71.2 | 63.7 |
| 1/4 | 50.4 | 41.7 |
| NO LOAD | 3.3 | 3 |
| LOCKED ROTOR | 24.9 | 26.8 |
| AMPS: | ||
| S.F. | 274 | |
| FULL | 239 | 213 |
| 3/4 | 185 | 170 |
| 1/2 | 137 | 133 |
| 1/4 | 99 | 105 |
| NO LOAD | 82.4 | 93.3 |
| LOCKED ROTOR | 1445.9 | 1471.1 |
| NEMA CODE LETTER | G | H |
| NEMA DESIGN LETTER | B | B |
| FULL LOAD RPM | 1190 | 990 |
| NEMA NOMINAL / EFFICIENCY (%) | 95.8 | 95.9 |
| GUARANTEED EFFICIENCY (%) | 95 | 95 |
| MAX KVAR | 55.8 | 54.9 |
| AMBIENT (°C) | 40 | 40 |
| ALTITUDE (FASL) | 3300 | 3300 |
| SAFE STALL TIME-HOT (SEC) | 30 | 30 |
| SOUND PRESSURE (DBA @ 1M) | 75 | 72 |
| TORQUES: | ||
| BREAKDOWN{% F.L.} | 240 | 285 |
| LOCKED ROTOR{% F.L.} | 150 | 185 |
| FULL LOAD{LB-FT} | 883.4 | 794.5 |
NEMA Nominal and Guaranteed Efficiencies are up to 3,300 feet above sea level and 25 ° C ambient
| The Above Data Is Typical, Sinewave Power Unless Noted Otherwise | ||
| NIDEC MOTOR CORPORATION |
|
Nidec trademarks followed by the ® symbol are registered with the U.S. Patent and Trademark Office. | ||